IEC 61000-2-2 pdf download – Electromagnetic compatibility (EMC) – Part 2-2: Environment – Compatibility levels for low- frequency conducted disturbances and signalling in public low-voltage power supply systems

admin
IEC 61000-2-2 pdf download – Electromagnetic compatibility (EMC) – Part 2-2: Environment – Compatibility levels for low- frequency conducted disturbances and signalling in public low-voltage power supply systems

IEC 61000-2-2 pdf download – Electromagnetic compatibility (EMC) – Part 2-2: Environment – Compatibility levels for low- frequency conducted disturbances and signalling in public low-voltage power supply systems
1 Scope and object
This standard is concerned with conducted disturbances in the frequency range from 0 kHz to9 kHz,with an extension up to 148,5 kHz specifically for mains signalling systems. It givescompatibility levels for public low voltage a.c. distribution systems having a nominal voltage upto 420 v, single-phase or 690 v, three-phase and a nominal frequency of 50 Hz or 60 Hz.
The compatibility levels specified in this standard apply at the point of common coupling.At thepower input terminals of equipment receiving its supply from the above systems the severityievels of the disturbances can, for the most part, be taken to be the same as the levels at thepoint of common coupling. In some situations this is not so,particularly in the case of a longline dedicated to the supply of a particular installation,or in the case of a disturbancegenerated or amplified within the installation of which the equipment forms a part.
Compatibility levels are specified for electromagnetic disturbances of the types which can beexpected in public low voltage power supply systems, for guidance in:
the limits to be set for disturbance emission into public power supply systems (including theplanning levels defined in 3.1.5).
the immunity limits to be set by product committees and others for the equipment exposedto the conducted disturbances present in public power supply systems.
The disturbance phenomena considered are:
– voltage fluctuations and flicker;
– harmonics up to and including order 50;- inter-harmonics up to the 5o”h harmonic;
– voltage distortions at higher frequencies (above the 50t harmonic);
voltage dips and short supply interruptions;
voltage unbalance;
transient overvoltages;power frequency variation;d.c.components;
– mains signalling.
Most of these phenomena are described in lEC 61000-2-1. In cases where it is not yet possibleto establish compatibility levels, some information is provided.
References normatives
Les documents de reference suivants sont indispensables pour lapplication du presentdocument. Pour les references datees,seule ‘edition citee s’applique.Pour les references nondatees, la derniere edition du document de reference sapplique (y compris les eventuelsamendements).
CEI60050-101,Vocabulaire Electrotechnique International(VEl) -Chapitre 101:Mathematiques
CEI60050-161,Vocabulaire Electrotechnique International (VEI) – Chapitre 161:Compatibiliteelectromagnetique
CEI 60664-1,Coordination de lisolement des materiels dans les systemes (reseaux) a bassetension – Partie 1 : Principes, prescriptions et essais
CEITR3 61000-2-1,Compatibilite electromagnetique (CEM) – Partie 2: Environnement -Section 1: Description de renvironnement – Environnement electromagnetique pour lesperturbations conduites basse frequence et la transmission de signaux sur les reseaux publicsd ‘alimentation
CEI 61000-3-3,Compatibilite electromagnetique (CEM) – Partie 3: Limites – Section 3:Limitation des fluctuations de tension et du flicker dans les reseaux basse tension pour lesequipements ayant un courant appele≤ 16A
CEI 61000-4-7,Compatibilite electromagnetique (CEM) – Partie 4:Techniques d’essai et demesure – Section 7: Guide general relatif aux mesures d’harmoniques et d’interharmoniques,ainsi qu’a ‘appareillage de mesure, applicable aux reseaux d’alimentation et aux appareils quiy sontraccordes
CEI 61000-4-15,Compatibilite electromagnetique (CEM) – Partie 4:Techniques d’essai et demesure -Section 15:Flickermetre -Specifications fonctionnelles etde conception
3Definitions
Pour les besoins de la presente partie de la CEl 61000,les definitions donnees dans laCEI 60050-101,la CEi 60050-161 et ses amendements 1 et 2 ainsi que les suivantess’appliquent.
3.1Definitions generales
3.1.1
perturbation (electromagnetique)
tout phenomene electromagnetique qui, de par sa presence dans lenvironnementelectromagnetique, peut faire devier un equipement electrique de sa performance attendue
[VEI 161-01-05,modifiee]
3.1.2
niveau de perturbation
amplitude d’une perturbation electromagnetique,mesuree et evaluee au moyen d’une methodespecifiee
[VEI 161-03-01,modifiee]