IEC 60255-1 pdf download – Measuring relays and protection equipment – Part 1: Common requirements
1 Scope
This part of lEC 60255 specifies common rules and requirements applicable to measuringrelays and protection equipment including any combination of devices to form schemes forpower system protection such as control, monitoring and process interface equipment in orderto obtain uniformity of requirements and tests.
All measuring relays and protection equipment used for protection within the power systemenvironment are covered by this standard.Other standards in this series may define their ownrequirements which in such cases shall take precedence.
For special applications (marine,aerospace,explosive atmospheres,computers,etc.), thegeneral requirements within this standard may need to be enhanced by additional specialrequirements.
The requirements are applicable only to relays in new condition.All tests in this standard aretype tests, unless otherwise declared.
2 Normative references
The following referenced documents are indispensable for the application of this document.For dated references, only the edition cited applies.For undated references, the latest editionof the referenced document(including any amendments) applies.
IEC 60044-1:1996,Instrument transformers – Part 1: Current transformers
IEC 60044-2:1997,Instrument transformers – Part 2: Inductive voltage transformersIEC 60044-5:2004, Instrument transformers – Part 5: Capacitor voltage transformersIEC 60044-7:1999,Instrument transformers – Part 7: Electronic voltage transformersIEC 60044-8:2002,Instrument transformers – Part 8: Electronic current transformers
IEC 60050-191:1990,Internation Electrotechnical Vocabulary – Chapter 191: Dependabilityand quality of service
IEC 60050-447:2009,International Electrotechnical Vocabulary – Part 447: Measuring relaysIEC 60068-2-1:2007,Environmental testing – Part 2-1: Tests – Test A: Cold
IEC 60068-2-2:2007,Environmental testing – Part 2-2: Tests – Test B: Dry heat
IEC 60068-2-14:2009,Environmental testing – Part 2-14: Tests – Test N: Change oftemperature
IEC 60068-2-30:2005,Environmental testing – Part 2-30: Tests – Test Db: Damp heat, cyclic12h + 12 h cycle)
IEC 60068-2-78:2001,Environmental testing – Part 2-78: Tests – Test Cab: Damp heat,sfeady state
IEC 60068-3-4;2001,Environmental testing – Part 3-4; Supporting documentation andguidance – Damp heat fests
IEC 60255-11:2008,Measuring relays and protection equipment – Part 11: Voltage dips, shortinterruptions, variations and ripple on auxiliary power supply port
IEC 60255-21-1:1988,Electrical relays – Part 21-1: Vibration,shock, bump and seismic testson measuring relays and protection equipment – Vibration fests (sinusoida)
IEC 60255-21-2:1988,Electrical relays – Part 21-2: Vibration,shock,bump and seismic testson measuring relays and protection equipment -Shock and bump tests
IEC 60255-21-3:1993,Electrical relays – Part 21-3;Vibration,shock,bump and seismic testson measuring relays and protection equipment – Seismic tests
IEC 60255-22-2:2008,Measuring relays and protection equipment – Part 22-2:Electricaldisturbance tests – Electrostatic discharge tests
IEC 60255-22-4:2008, Measuring relays and protection equipment – Part 22-4: Electricaldisturbance fests – Electrical fast transient/burst immunity fest
IEC 60255-22-5:2008,Measuring relays and protection equipment – Part 22-5: Electricaldisturbance tests -Surge imrunify test
IEC 60255-22-7:2003,Electrical relays – Part 22-7:Electrical disturbance tests for measuringrelays and protection equipment – Power frequency immunity tests
IEC 60255-25;2000,Electrical relays – Part 25: Electromagnetic emission tests for measuringrelays and protection equipment
IEC 60255-26:2008,Measuring relays and protection equipment – Part 26: Electromagneticcompatibiity requirements
IEC 60255-27:2005,Measuring relays and protection equipment – Part 27: Product safetyequipment
IEC 60255-100(all parts), Measuring relays and protection equipment – Parts 1XX: Protectionfunctional standards
IEC 60297-3-101:2004,Mechanical structures for electronic equipment – Dimensions ofmechanical structures of the 482,6 mm (19 in) series – Part 3-101: Subracks and associatedplug-in units
IEC60529:1989,Degrees of protecfion provided by enclosures (IP Code)
IEC 60688,Electrical measuring transducers for converting a.c. electrical quantities toanalogue or digital signals
IEC 60721-3-3,Classification of environmental conditions – Part 3-3: Classification of groupsof environmental parameters and their severities – Stationary use at weather-protectedlocations
IEC/TR 61000-2-5:1995,Electromagnetic compatability (EMC) – Part 2: Environment -Section 5: Classification of electromagnetic environments -Basic EMC publication
IEC 61810-1,Electromechanical elementary relays – Part 1: General requirements
IEC 61810-2,Electromechanical elementary relays – Part 2: Reliability
IEC 61850(all parts), Communication networks and systems in substations
IEC 61850-9-2,Communication networks and systems in substations – Part 9-2:SpecificCommunication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3
3Terms and definitions
For the purposes of this document, the terms and definitions of lEC 60050-447, as well as thefollowing. apply.
3.1
absolute error
difference between a measured operate value of the characteristic quantity or a measuredvalue of a specific time and its declared value (e.g. setting value).
3.2
alternating component
in d.c. expressed as a percentage of the difference between the maximum value Umax and theminimum ‘value umin of a pulsating d.c. voltage to the mean value u, of this voltage
max – Umin _x100%
uo
3.3
analogue inputs and outputs
current or voltage inputs/outputs whose values are directly proportional to physical measuredquantities i.e. transducer input
3.4
assigned error
error limits within which the manufacturer declares that any device of a given type will performunder the reference conditions